Liquid Circulation Heat Exchanger
Working Principle
Liquid circulation heat exchanger is liquid to air heat exchanger, heat exchangers installed in both fresh air side and exhaust air side, the pump between the 2 heat
exchangers make the liquid circulate then the heat in the liquid preheat or precool the fresh air. Normally the liquid is water but in order to decrease the freezing point,
moderate ethylene glycol will be added into the water according to reasonable percentage.
Features
(1) Fresh air and exhaust air heat exchanged by separated liquid pipes, zero cross contamination.Suitable for hospital, germfree lab and industries which discharge
poisonous and harmful gas.
(2) Stable and reliable operation, long service life
(3) Flexible connection between fresh air and exhaust air exchangers, easy installation which is convenient for old AHU improvement.
(4) Accessories like water pump, heat exchangers are conventional, easy and low maintanence costs.
(5) Wide range of application, various connection ways like one to one, one to many or many to many.
Specifications
(1) Liquid circulation heat exchanger is sensible heat exchanger, efficiency is between 55% to 60%.
(2) Suggested rows are 6 or 8, face velocity not over 2.8m/s
(3) The choice of circulating pump can refer to the fresh air and exhuast air pressure drop and the waterflow pressure drop.
(4) Air flow direction has significant effect on the heat recovery efficiency, influence rate up to 20%.
(5) Freezing point of the hybrid ethylene glycol and water should be 4 to 6 celsius lower than the local minimum winter outdoor temperature, percentage of hybridcan
be refered to the following table.
Freezing point | -1.4 | - 1.3 | -5.4 | -7.8 | -10.7 | -14.1 | -17.9 | -22.3 |
Weight percentage (%) | 5 | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
Volume percentage (% ) | 4.4 | 8.9 | 13.6 | 18.1 | 22.9 | 27.7 | 32.6 | 37.5 |
Product detail pictures:
Related Product Guide:
Coffee shop chemicals: Stone Creek takes steps to protect employees | Fresh Air Ventilation Systems
Cincinnati Streetcar: Mold found in ventilation system | Fresh Air Ventilation Systems
We have now a hugely efficient team to deal with inquiries from buyers. Our goal is "100% client gratification by our solution high-quality, rate & our team service" and take pleasure in a great popularity among clients. With several factories, we will provide a wide assortment of Factory directly supply Ceil Air Handling Units - Liquid Circulation Heat Exchangers – Holtop, The product will supply to all over the world, such as: Bhutan, Niger, Johannesburg, We also have the strong ability of integration to supply our best service, and plan to build the warehouse in the different countries around the world, that will probably be more conveniently to service our customers.
Heat Recovery Ventilator
Single Room Heat Recovery Ventilator
Heat Recovery Ventilators
Hrv Heat Recovery Ventilator
Ductless Heat Recovery Ventilator
By Alan from Azerbaijan - 2015.11.02 11:11
This enterprise in the industry is strong and competitive, advancing with the times and develop sustainable, we are very pleased to have a opportunity to cooperate!
By June from Grenada - 2016.04.28 15:45